Contacts: Four galvanically-isolated relay contacts
Contact Arrangement: SPST (1 Form A)
Nominal Switching Capacity (resistive load): 5 A 250 VAC, 5 A 30V DC
Max Switching Power: 1.25 kVA AC, 150 W DC
Max Switching Voltage: 250 VAC, 110 VDC (0.4A)
Max Run Current: AC 5 A continuous (convective) DC 5 A continuous (convective), simultaneous operation of all relays
Contact Resistance: Max 30 mΩ (10 mΩ typical)
Dry Circuit Capability: 1 mA @ 5 V
Breakdown Voltage (initial) Between Open Contacts: 1000 Vrms for 1 min
Breakdown Voltage (initial) Between Contact and Coil: 3000 Vrms for 1 min
Surge Breakdown Voltage (initial) Between Contact and Coil: 6000 V (±1.5×50µs per JEC-212-1981)
Operate Time: 10 ms max (excluding bounce)
Release Time: 5 ms max
Max Operating Speed: 20 times/minute
Mechanical Life: Min 2×107 (@180 times/min)
Electrical Life: Min 105 (DC resistive); 5 x 104 (AC resistive)
Relay Standard: Complies with IEC 61010-2-201 for reinforced insulation and hazardous-location use per ANSI/ISA 12.12.01
Relay Inductive Load Driver: Integrated MOSFET switch, ESD protection and Zener Diode clamps (no free-wheeling diode, Zener clamps route induced current to ground for electrically quiet system operation)
Fan Enable: Any relay enabled
Relay Contact State Indicators: Four bicolor (red = high, green = low) LEDs with adjustable pulse width modulation (PWM) illumination control
Control: I2C (operate & release functions)
Field Connector: Phoenix Contact 9-circuit; not supplied
Power: +5 VDC @ 6 mA idle, 94 mA four-relays enabled (22 mA/relay)
Maximum Installed Modules: 10 (maximum of 24 relays enabled at a time)
Weight: 1.4 oz